Power Factor Correction Systems
Control Systems
Consulting • Planning • Design
ELKON Power Factor Correction Systems
Systems with Reactor Protection
select:
Home | About us | News | Contact | Download | Elkon Kompensationsanlagen
Power factor correction system in modular design, wired ready for connection, for central power factor correction in supply lines with harmonics

Manufactured to DIN VDE 0560, DIN VDE 0660, IEC 439, IEC 70/831
Rated voltage 400 V 50 Hz
Ambient temperature max. 35°C
Rated power 150 - 1200 kvar andere Leistungen auf Anfrage
Casing sheet steel cabinet IP 30 cable entry from the top or from the bottom as required by the customer
Capacitors self-healing PCB-free MKP-type capacitors with overpressure tear-off fuses filled with biodegradable oil power loss at connection terminals: less than 0.3 W/KVAR optional: dry capacitors capacitors are discharged using resistors or, optionally, using a discharge reactor
Contactors special capacitor contactors
Protection group protection using HRC load breaker
Filter circuit reactors detuning factor 5-16%, with over-temperature monitoring low-loss, highly linear design insulation class T40/B
- Designs for rated voltages of 208 V, 400 V, 525 V, 690 V are available.

Optionally available:

- systems with overcurrent relays
- systems with quick discharge reactors
- systems with audio frequency blocking device
- combination filter systems
Download data sheets, manuals and texts of specifications...