| Ready-to-be-installed power factor correction modules for cabinets 600, 800
and 850 mm in width, may be extended easily, plug-type connection
Manufactured to DIN VDE 0560, DIN VDE 0660, IEC 439, IEC 70/831 |
| Rated voltage | 400 V 50 Hz |
| Ambient temperature | max. 35°C |
| Rated power | 5-200 kvar |
| Capacitors | self-healing PCB-free MKP-type capacitors with
overpressure
tear-off fuses filled with biodegradable oil power loss at connection terminals: less than 0.3 W/KVAR optional: dry capacitors capacitors are discharged using resistors or, optionally, using a discharge reactor |
| Contactors | special capacitor contactors
with protective resistors to limit inrush current |
| Protection | group protection using HRC load breaker |
| Delivery includes the following | power factor correction module
busbar connectors busbar cover for protection against contact connector for control system |
| Order installation rails for switch cabinet separately, depending on the type and installation depth of the switch cabinet used. |
![]() |
| Download data sheets, manuals and texts of specifications... |